Inverter size calculator

Size an inverter from a load list: continuous watts should cover the running total; surge watts should cover the starting total. You type each load; optional headroom is a percentage you enter.

Loads that run together

Type starting watts from the nameplate or manufacturer. The calculator uses the starting watts you type; it does not apply a built-in motor multiplier.

Continuous rating ≥ running total; surge rating ≥ starting total. Starting total uses other running loads plus the largest surge increment, assuming one motor starts at a time.

Enter values to see the result.

Results are estimates. Check ratings with the manufacturer, and use a qualified electrician for installation.

What size inverter do I need?

An inverter turns a battery’s DC into AC. Its continuous (rated) watts should cover the running total of the loads that will be on together. Its surge watts should cover the starting total. Unlike a generator, it does not make fuel or exhaust, but it does draw DC current from the battery, and that current sets cable and fuse sizing, which needs a qualified electrician.

Example, with the same labelled list as a typical generator check: a refrigerator at 200 W running and 600 W starting, lighting at 100 W, and a microwave at 1,000 W. Running total 1,300 W; starting total 1,700 W. Choose an inverter of at least 1,300 W continuous and 1,700 W surge (1,560 W and 2,040 W if you add 20% headroom).

At 12 V, a 1,300 W AC load would draw 1,300 ÷ 12 = 108.3 A from the battery if the inverter were 100% efficient. Real current is higher once you include inverter losses: at 90% efficiency it is 1,300 ÷ (12 × 0.90) = 120.4 A.

What size inverter do I need?

At least the running total for the continuous rating, and at least the starting total for the surge rating, using starting watts from the labels. Then check that the battery and cabling can supply the DC current at your battery voltage.

How many amps does an inverter draw from a 12 V battery?

Divide the AC load watts by (battery volts × inverter efficiency). At 12 V and 100% efficiency, 300 W is 25 A and 1,300 W is 108.3 A, as in the table below. Lower efficiency increases the current.

Continuous vs surge watts

Continuous watts are what the inverter can supply steadily. Surge watts are a short allowance for motor starts. The starting total uses other running loads plus the largest surge increment, assuming one motor starts at a time. That is the same totalling rule as on the generator calculator, applied here to the inverter’s two ratings.

Inverter and battery voltage

Higher battery voltage means lower DC current for the same AC load, which is why 24 V and 48 V systems are common as loads grow. The table is DC current at 100% inverter efficiency; divide by your efficiency if you have it.

Battery current from AC load watts at 100% inverter efficiency
AC load12 V24 V48 V
300 W25.0 A12.5 A6.3 A
1,000 W83.3 A41.7 A20.8 A
1,300 W108.3 A54.2 A27.1 A
3,000 W250.0 A125.0 A62.5 A

Methodology and sources

Running total R is the sum of running watts for loads that run together. Choose an inverter whose continuous rating is at least that figure (after any headroom you enter).

Starting total: R − R_max + S_max, where max is the load with the largest surge increment (S_i − R_i). The inverter’s surge rating should be at least that figure.

Optional user-entered headroom (%) is applied after, to both figures.

This is common manufacturer-guide practice for running versus starting watts, not a numbered IEC or NEC formula.

Enter starting watts from each appliance label. The calculator uses the starting watts you type; it does not apply a built-in motor multiplier. Battery current at a chosen DC voltage is load watts divided by battery volts (higher if you include inverter losses). Cable and fuse sizing needs a qualified electrician.

For appliance energy from watts and time, use the appliance energy calculator.