Solar battery calculator
Estimate nameplate battery-bank energy from your daily load, days of autonomy, depth of discharge and round-trip efficiency. You enter depth of discharge and η for the chemistry you are using.
Type depth of discharge and efficiency as fractions. There are no built-in chemistry defaults.
Enter values to see the result.
Bank size comes from the daily load, days of autonomy, DoD and efficiency you type. It is not PVWatts, not a location tool, and not a payback estimator.
Results are estimates. Check ratings with the manufacturer, and use a qualified electrician for installation.
Battery bank size in kWh and Ah
Nameplate energy is kWh = (daily kWh × days of autonomy) ÷ (DoD × η). Amp-hours at a chosen battery voltage are Ah = (kWh × 1,000) ÷ volts.
Example: 3 kWh/day, 2 days of autonomy, 80% depth of discharge and 90% round-trip efficiency. Nameplate energy is (3 × 2) ÷ (0.80 × 0.90) = 8.33 kWh. At 12 V that is 694 Ah; at 24 V, 347 Ah; at 48 V, 174 Ah.
| Daily use | 1 day | 2 days | 3 days |
|---|---|---|---|
| 1 kWh/day | 1.39 kWh | 2.78 kWh | 4.17 kWh |
| 3 kWh/day | 4.17 kWh | 8.33 kWh | 12.50 kWh |
| 5 kWh/day | 6.94 kWh | 13.89 kWh | 20.83 kWh |
| 10 kWh/day | 13.89 kWh | 27.78 kWh | 41.67 kWh |
How big a battery bank do I need?
Start from daily kWh and how many days you want to cover without sun, then enter the depth of discharge and efficiency the manufacturer supports. The 8.33 kWh example above is one such combination, not a default for every chemistry. For an RV-sized bank, see RV solar. Series and parallel wiring is on series vs parallel.
Days of autonomy
Days of autonomy is how many days of the stated daily load the bank should cover without charging. One day is a thinner reserve; three days is a larger pack, as the table shows. It is a design choice you enter, not a figure the calculator supplies.
Series and parallel for 12, 24 and 48 V
The energy in kWh does not change with voltage; the amp-hour figure does. The 8.33 kWh example is 694 Ah at 12 V, 347 Ah at 24 V and 174 Ah at 48 V. Reaching 24 V or 48 V is usually done by placing 12 V batteries in series; adding capacity at the same voltage is done in parallel.
Methodology and sources
Nameplate energy for days of autonomy:
E_nameplate,kWh = (E_day,kWh × D) / (DoD × η)
Optional amp-hours at a battery voltage you enter: Q_Ah = E_Wh / V (with E_Wh = E_kWh × 1000).
Bank size is a common off-grid energy balance: nameplate kWh = (daily kWh × days of autonomy) ÷ (depth of discharge × round-trip efficiency). You enter depth of discharge and efficiency; there are no built-in chemistry defaults.