UPS runtime calculator

Estimate UPS discharge time from battery watt-hours, depth of discharge, efficiency and load, and a minimum VA size from watts and power factor. You enter each of those figures, including DoD and η.

Mode

DoD, efficiency and PF are values you type. No manufacturer runtime curve is fitted here.

Enter values to see the result.

A simple Wh/W (or VA) model is only an estimate. Real UPS runtime is not linear with load; use the manufacturer’s curve when you have one.

Results are estimates. Check ratings with the manufacturer, and use a qualified electrician for installation.

UPS size: VA from watts

A UPS is often rated in VA (or kVA) as well as watts. Minimum apparent power is VA = watts ÷ power factor. The calculator reports that figure from the load and the power factor you enter.

Example: a 300 W load on a 500 Wh battery, with depth of discharge 100% and efficiency 100%, has a linear runtime of 500 ÷ 300 = 1.67 hours (1 hour 40 minutes). If you enter 90% efficiency instead, usable energy is 450 Wh and the estimate is 1.50 hours.

Minimum VA from watts at two power factors
LoadPF 0.6PF 0.9
100 W167 VA111 VA
200 W333 VA222 VA
300 W500 VA333 VA
500 W833 VA556 VA
1,000 W1,667 VA1,111 VA

How long will a UPS last?

Use the linear estimate above as a starting point, then prefer the manufacturer’s runtime chart. Real UPS runtime is not a straight line with load, which is why the warning sits next to the result.

How many VA do I need for a PC?

Start from the PC’s watt rating (or a measured load) and divide by the power factor you have, or by 0.9 if the PSU lists a high power factor, or by a lower figure if you only know watts and want more VA headroom. A 300 W PC at PF 0.6 needs 500 VA; at PF 0.9 it needs 333 VA. Then choose a UPS whose watt rating also covers 300 W.

Why UPS runtime is not linear

Inverter efficiency, battery voltage sag and the way the UPS shares the load all change as the load changes. A pack that lasts 1.67 hours at 300 W in the linear model will not necessarily last 5 hours at 100 W in real life. Treat the result as an estimate and check the maker’s curve. The how a UPS works guide covers offline, line-interactive and online types.

Methodology and sources

Discharge time uses the same linear energy model as the battery runtime calculator:

t_h = (E_Wh × DoD × η) / P_W

Minimum apparent power before any user headroom: S_VA ≥ P_W / PF (you enter PF).

Runtime uses the same linear energy balance as the battery calculator: hours = Wh × DoD × η / load watts. Minimum VA is load watts divided by the power factor you enter. Real UPS runtime is not linear with load, so use the manufacturer’s chart when you have it. IEC 62040 is the standard family that classifies UPS performance. You enter depth of discharge and efficiency; there are no built-in defaults.

For Wh ↔ mAh at a voltage you type, use the mAh to Wh calculator.