Portable power station runtime calculator
Estimate portable power station or solar-generator runtime from capacity, depth of discharge, inverter efficiency and load. Optional solar recharge if you enter input watts and charge efficiency.
Type inverter and charge efficiency as fractions (for example 0.90). There is no built-in default.
Enter values to see the result.
Results are estimates. Check ratings with the manufacturer, and use a qualified electrician for installation.
How long will a power station run my loads?
At the AC outlets the estimate is hours = (Wh × DoD × inverter efficiency) ÷ load watts, unless solar input is covering part of the load.
Example: a 1,000 Wh unit, 100 W load, 100% depth of discharge and 85% inverter efficiency has usable energy of 850 Wh, so runtime is 8.5 hours, with no solar input.
| Nameplate energy | 50 W | 100 W | 500 W |
|---|---|---|---|
| 300 Wh | 5.10 h | 2.55 h | 0.51 h |
| 1,000 Wh | 17.00 h | 8.50 h | 1.70 h |
| 2,000 Wh | 34.00 h | 17.00 h | 3.40 h |
How long does a 1,000 Wh power station last?
With the 85% efficiency and 100 W load above, 8.5 hours. At 50 W it is 17 hours; at 500 W it is 1.7 hours. Enter your own depth of discharge and efficiency if the manufacturer gives them.
Solar input and recharge time
If the unit is also receiving solar (or other DC) input, the calculator subtracts that charging power, after the solar efficiency you enter, from the load. When input exceeds the load, the result is that the pack is gaining energy, not discharging. Recharge time with no load is energy to add divided by (solar watts × solar efficiency). This is still a linear estimate.
Methodology and sources
Runtime uses a linear energy model, typically at the AC output with an inverter efficiency you enter:
t_h = (E_Wh × DoD × η) / P_W
Optional solar recharge time: t_recharge,h = E_Wh,to add / (P_solar,W × η).
Net runtime while charging: if P_solar × η > P_load, the station is gaining energy. If they are equal, the station is balanced (holding). Otherwise runtime uses the net load P_load − P_solar × η with the same usable energy.
You enter inverter efficiency; there is no built-in default. The estimate is linear. Real runtime varies with inverter losses, temperature and the way the pack is discharged.
For capacity unit conversion, use the mAh to Wh calculator.