What is power factor?

Watts measure real power. Volt-amperes measure apparent power. Power factor is the ratio that connects them.

Real power, apparent power and PF = kW / kVA

Real power (watts or kilowatts) is the power that does useful work or becomes heat. Apparent power (volt-amperes or kilovolt-amperes) is the product of the voltage and current magnitudes for AC.

Power factor is defined as PF = P / S (real power divided by apparent power), or, in kilowatt units, PF = kW / kVA. Rearranged: kW = kVA × PF, and kVA = kW / PF. On the calculators, PF is a number between 0 and 1 (exclusive of 0).

That definition follows the usual engineering sense of power factor (IEEE Std 1459 / IEC 60050).

Single-phase apparent power is S_VA = V × I. Three-phase apparent power uses the line-to-line form with √3: S_VA = √3 × V_L-L × I.

Why a nameplate can show both VA and W

A motor or UPS nameplate often lists both a watt (or kilowatt) figure and a VA (or kVA) figure, or it lists VA and a power factor. The VA rating describes how much apparent power the supply and wiring must support; the watt rating describes real power delivered or drawn.

If PF is less than 1, the VA number is larger than the watt number for the same load. Sizing a UPS or inverter against the wrong column is a common mistake: a unit rated in VA may not support the same number of watts unless the power factor is taken into account.

Use the power factor from the nameplate or manufacturer data when you have it. If you leave PF at 1 on the calculator, treat the result as the limiting case for a resistive load.

Convert kW, kVA and amps

To convert between kVA and kW with a power factor you enter, or to get kVA from volts and amps, use the kVA to kW calculator. For watts and amps with a power factor you enter, use the watts to amps calculator. The three-phase form is explained on three-phase power. UPS sizing often starts from VA and watts together; see how a UPS works and the UPS runtime calculator.